Energy efficient
• LED technology provides industry’s lowest current draw for a combined high and low candela device
• Fewer power supplies required, smaller wire gage, reduced wire runs
Compatibility
• UL/ULC listed as compatible with all Fire Alarm Control Panels (FACP) and accessories that have been determined to be compatible with Wheelock RSS strobe-based products and Exceder LED3
• Ability to mix LED and xenon strobes in the same field of view
• Meets stringent synchronizing standards for strobes with Wheelock’s DSM Sync Modules, PS Power Supplies or SAFEPATH products
Low profile design
• One of the smallest, most compact single-gang designs
• Sleek, modern aesthetics with no visible mounting screws
Special lettering
6 Field selectable settings
• Wall: 15, 30, 75, 110, 135, 185 cd
Easy-to-install
• Mounting plate included with all models: Convenient capture hinge allows installers to easily hold the device while fastening the single-mount screw in place
• Pre-wire/pre-test capability to check for wiring and ground faults prior to appliance installation
• Finger slide switches--No tools needed for setting changes
• IN/OUT screw terminals using #12 to #18 AWG wires
• Mounting options include ELSBB, any single-gang backbox and to 4” square with adapter kit for wall models and LSPKBB-C backboxes, 4” square, 1 1/2” or 2 1/8”deep and 4” Octagonal, 1 ½” or 2 1/8”deep for ceiling models
Compliance & approvals
• NFPA 72 2016 (meets maximum light pulse duration of 20 ms)
• UL 1971, UL 1638, UL 464; ULC-S525, ULC-S526
• California State Fire Marshal (CSFM)
• ADA/NFPA/ANSI/OSHA
Wall: 15, 30, 75, 110, 135, 185 cd